Description
Conductor: Class 2 Plain Annealed Copper
Insulation: PVC V-90
Core Identification
Red, Green, Yellow, Blue, Black, White, Yellow/Green, or as per Client Requirement
Technical Data
Voltage Rating: 0.6/1kV
Operating Temperature: -25°C to +75°C, Maximum 90°C*
*Not subject to severe mechanical pressure at temperatures higher than 75°C.
Short Circuit Temperature: 160°C for 5 sec
Standards Compliance
AS/NZS 5000.1
AS/NZS 3808
AS/NZS 1125
AS/NZS 1660.5.6 (Equivalent to IEC 6032-1)
Send Inquiry

This PVC-insulated single-core building wire is designed for fixed low-voltage electrical wiring in residential, commercial, and industrial buildings across Australia and New Zealand, in compliance with local electrical standards.
- General power distribution for lighting, power sockets, air conditioners, water heaters, and other electrical appliances.
-
Internal wiring of distribution boards, switchboards, and control cabinets.
-
Earthing circuits with green/yellow conductors.
-
Wiring for ventilation, pumping equipment, and general industrial machinery.
-
Installation in conduits, trunking, enclosed cable trays, wall cavities, and underground ducts.
Notes
- For fixed installation only, not suitable for flexible or mobile equipment.
- Indoor use or outdoor areas with UV protection; not for direct exposure to sunlight.
- Rated voltage: 0.6/1 kV, for low-voltage power systems.